Ahwaz Electromechanical Technology

Focusing on Instrumentation: Competitive Pricing with Swift Delivery

Rosemount214CRTDTemperatureSensorand148TemperatureTransmitter-AhwazAutomation|ProcessControls|AhwazMeasurementInstruments

Temperature Sensors/

Rosemount 214C RTD Temperature Sensor and 148 Temperature Transmitter

Specifications Rosemount 214C RTD Temperature Sensor Temperature Range: For wire-wound element, 0.05 °C (0.020 ) maximum ice-point resistance shift after 1g vibration between 20 and 500 Hz for 150 hours according to IEC 60751:2008 Lead Wires: 24 AWG wire, FEP insulated; color coded per IEC 60751 Time Constant / Response: 10.8 seconds maximum required to reach 50% sensor response when tested in flowing water according to IEC 60751:2008 Stability: ±0.15 °C (0.059 ) maximum ice-point resistance shift following 1,000 hours at maximum specified temperature when measured per methods defined in IEC 60751:2008 Insulation Resistance: 1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature Calibration Options: IEC 751 Class A or B; Single point calibration; Calibration schedule…

  • Product Details

Specifications

Rosemount 214C RTD Temperature Sensor
Temperature Range: For wire-wound element, 0.05 °C (0.020 ) maximum ice-point resistance shift after 1g vibration between 20 and 500 Hz for 150 hours according to IEC 60751:2008
Lead Wires: 24 AWG wire, FEP insulated; color coded per IEC 60751
Time Constant / Response: 10.8 seconds maximum required to reach 50% sensor response when tested in flowing water according to IEC 60751:2008
Stability: ±0.15 °C (0.059 ) maximum ice-point resistance shift following 1,000 hours at maximum specified temperature when measured per methods defined in IEC 60751:2008
Insulation Resistance: 1000 MΩ minimum insulation resistance when measured at 500 VDC at room temperature
Calibration Options: IEC 751 Class A or B; Single point calibration; Calibration schedule or customer-specified calibration range, both with Callendar-Van Dusen constants
Rosemount 148 Temperature Transmitter
Input: Single sensor capability with universal sensor inputs (RTD, T/C, ohms)
Output Signal: 4-20 mA Analog
Housing: DIN B head mount
Certifications/Approvals: Hazardous location, see full specs for complete list of certifications

 

Features

Rosemount 214C RTD Temperature Sensor
  • Single or dual element Pt-100 RTD with thin-film or wire-wound designs meets various application requirements
  • Thin film sensor engineered to withstand high vibration industrial applications
  • Wire-wound design for applications requiring high accuracy, dual-elements and/or are subjected to high temperatures
  • Covers a wide range of temperatures from –321 to 1112°F (–196 to 600°C) for application flexibility
  • Callendar-Van Dusen constants allow for transmitter-sensor matching and offer the highest level of accuracy
  • Optional Class A accuracy ensures critical temperature measurement points meet tolerance and accuracy standards
  • Adaptable design with a variety of enclosure and connection head options meet varying application demands
  • Includes spring-loaded or compact spring-loaded mounting styles for adaptability
  • North American approvals meet hazardous location requirements
Rosemount 148 Temperature Transmitter
  • Device used with multiple sensor type inputs for adaptability
  • DIN B style head mount with a variety of DIN B enclosure options provides a cost-effective solution
  • 4 to 20 mA signal withstands noise for reliable performance in process environments
  • Ambient temperature compensation enhances performance and process quality
  • PC-based HART configuration interface delivers necessary programmer, cables and software for transmitter configuration