Specifications
Rosemount 214C Thermocouple Temperature Sensor
- Insulation Resistance: 1000 MΩ minimum insulation resistance when measured at 500VDC at room temperature
- Certifications/Approvals: Hazardous location, see full specs for complete list of certifications
- Lead Wires: 24 AWG wire, FEP insulated. Color coded per IEC 60584 or ASTM E230.
- Insulation Resistance: 1000 MΩ minimum insulation resistance when measured at 500VDC at room temperature
- Certifications/Approvals: Hazardous location, see full specs for complete list of certifications
Rosemount 248 Head Mount Temperature Transmitter
- Input: Single sensor capability with universal sensor inputs (RTD, T/C, mV, ohms)
- Output Signal: 4-20 mA /HART protocol
- Housing: DIN B head mount
- Diagnostics: Basic diagnostics including open/short sensor diagnostics
- Calibration Options: 5-point calibration
- Certifications/Approvals: SIL 2/3 certified to IEC 61508 by an independent 3rd party, hazardous location, marine type, see full specs for complete list of certifications
Features
Rosemount 214C Thermocouple Temperature Sensor
- Sensor types include J, K and T thermocouples for application flexibility
- Meets ASTM and IEC standards for thermocouple accuracy tolerance, providing reliable performance
- Covers a wide range of temperatures from -196 to 1200 °C (-321 to 2192 °F) for durability in varying process environments
- Withstands high vibration to offer resilience in tough process conditions
- Available in single or dual configurations with grounded or ungrounded junctions for process compatibility
- All sensor styles and lengths are available in ¼-in. diameter mineral-insulated (MI) cable to meet industry standards
- Adjustable or fixed compression fittings and spring-loaded or welded adapters meet specific mounting requirements
- Enclosure and connection head options allow for process adaptability
- Global hazardous location approvals to meet project requirements
Rosemount 248 Head Mount Temperature Transmitter
- Standard transmitter meets common single point temperature measurement application requirements
- Housing construction provides superior resistance to many process environments
- One-year stability rating reduces maintenance costs
- Open/short sensor diagnostics help detect issues in the sensor loop to ensure reliable performance
- Device dashboards provide easy interface for simplified device configuration and diagnostic troubleshooting
- Transmitter-sensor matching with Callendar-Van Dusen constants reduces total measurement error