Certifications – cULus | - PD100 cULus listed General Purpose and Non-Incendive, ATEX/IECEx, CE
PD200 cULus listed General Purpose and Intrinsically Safe, ATEX/IECEx, CE
|
Environmental Ratings | IP66, Type 4X |
Communications Protocol | - (PD100) 4-20 mA (nominal)
(PD200) HART Capable
|
Configurable Alarms | - (PD100) No
(PD200) Yes
|
Minimum Voltage | - (PD100) 8.5 VDC for analog control
(PD200) 8.5 VDC for analog control, 9.0 VDC for HART communication
|
Overvoltage | 36 VDC |
Voltage Drop | 12.2 VDC @ 4mA/24 VDC |
Input Impedance | 470 ohms @ 20mA/24 VDC |
Output Impedance (Feedback) | 800 ohms @ 20mA/24 VDC |
Actuator Signal | 0% to 100% of the supply pressure |
Response Time | ≥ 0.3% of Full Scale |
Stroke Range | - Linear: 12 to 200 mm
Rotary: 0 to 120°
|
Hysteresis | 1.5% of Full Scale |
Repeatability | 1.5% of Full Scale |
Linearity | 0.8% of Full Scale |
Temperature Range | -40°C to +65°C (-40°F to +149°F) |
Electrical Connection | 1/2″ NPT female |
Pneumatic Connection | 1/4″ NPT female (Inlet & Outlet) |
Air-Supply Pressure | 2.8 to 8 bar (40 to 116 psi) |
Output Air Consumption | 8.81 l/m | 0.5N m³/h | 0.31 scfm @ 60 psi | 4 bar | 0.6 cv |
Display Type | - (PD100) Liquid Crystal Display (LCD), 4 numeric digits
(PD200) Liquid Crystal Display (LCD), 4.5 numeric digits and 6 alphanumeric digits
|
Local Controls | - (PD100) 3 mechanical buttons | Up, Down, & Enter
(PD200) 3 mechanical & 3 magnetic buttons | Up, Down, & Enter (Includes magnetic key for operation without removing cover)
|
Actuator Action | Rotary & Linear, Single & Double, Direct (DA) & Reverse (RA) |